System power supply has not been considered for calculating the figures for actuator and
actuator controls.
As previously mentioned in the architecture section, safeguarding power supply and
resulting calculations are the responsibility of the plant operator.
The plant operator is responsible for complying with assumed MTTR. Otherwise the data of
the quantitative results is no longer valid.
The safety figures mentioned in this safety manual are only valid if all the conditions
stipulated in this safety manual and the mentioned activities are respected.
The PFD values specified in this safety manual are only examples and subject to certain
assumptions e.g. on T , MTTR, …
proof
The PFD calculation should always be performed individually for each system using the
parameters and conditions applicable for the respective system. The λ and λ values
DU DD
should be used as input. When observing the proof test procedures indicated in this safety
manual, we recommend using a proof test coverage (PTC) of 90 % for the calculations.
· The calculation of the safety figures is based on the indicated safety functions.
Hardware assessments are based on Failure Modes, Effects and Diagnostic Analysis
(FMEDA). FMEDA is a step to assess functional device safety in compliance with IEC
61508. On the basis of FMEDA, the failure rates and the fraction of safe failures of a
device are determined.
· Experience data and data taken from the exida database for mechanical components
is used to calculate mechanical failure rates. The electronic failure rates as base failure
rates are taken from the SIEMENS Standard SN 29500.
· In compliance with table 2 of IEC 61508-1, the average target PFD values for systems
with low demand mode are:
- SIL 2 safety functions: = 10
-3
to < 10
-2
- SIL 3 safety functions: = 10
-4
to < 10
-3
Since actuators only represent a part of the overall safety function, the actuator PFD
should not account for more than approx. 25 % of the permissible total value (PFD
avg
)
of a safety function. This results in the following values:
- Actuator PFD for SIL 2 applications: 2.5E-03
· Electric actuators with actuator controls are classified as type A components with a
hardware fault tolerance of 0. The SFF for the type A subsystem should be between
60% and <90 % according to table 2 of IEC 61508-2 for SIL 2 (subsystems with a
hardware fault tolerance of 0).
Figure 16: Non-normative failure distribution assumed by AUMA