EasyManua.ls Logo

AUMA SAR 07.1 - SAR 30.1 - Push Button Operations

AUMA SAR 07.1 - SAR 30.1
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Push buttons
If the selector switch is in position local control (I), use the push buttons
OPEN - STOP - CLOSE to operate the actuator locally.
OPEN: Actuator runs in direction OPEN
STOP: Actuator stops
CLOSE: Actuator runs in direction CLOSE
The operation commands OPEN - CLOSE can be used for control during
push-to-run operation or in the self-retaining mode.
In the push-to-run operation, the actuator runs as long as the push button is
pressed.
In the self-retaining mode, the actuator runs to the defined end position,
unless another command has been received beforehand.
For further information on the programming, refer to page 33.
Indication lights
The 3 indication lights give the following signals (standard indication).
Illuminated (green): Actuator is in end position OPEN
Collective fault signal (red)
IIlluminated (yellow): Actuator is in end position CLOSED
Collective fault signal:
The collective fault signal (red indication light) will be activated if one of the
following events occurs:
.
Torque fault, i.e. the set torque (page 24) was exceeded before reaching
an end position.
.
Motor protection has tripped (refer to page 49), i.e. the motor is overheated.
.
A phase failure (for 3-phase AC motors) has occurred.
.
Test PTC tripping device
Indication lights are blinking:
If the actuator is equipped with a b
linker, the indication lights can be used as
running indication.
If the blinker transmitter is active (page 33), the respective indication light
blinks during operation.
20
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1/AM 02.1 Operation instructions

Table of Contents