22.3 Setting ON and OFF times
ON and OFF times can be set independently of each other between 1 – 30
seconds at the 4 potentiometers R10 to R13.
Clockwise rotation: Time extension
Counterclockwise rotation: Time reduction
R10 (t-off) : OFF time in direction OPEN
R11 (t-on) : Running time in direction OPEN
R12 (t-off) : OFF time in direction CLOSE
R13 (t-on) : Running time in direction CLOSE