SE6166 Controller • Rev. 4/13/2011 4 © 2011 Automated Logic Corporation
The SE6166 has 6 analog outputs that support voltage or current devices. The controlled
device must share the same ground as the controller and have the following resistance to
ground:
0–10 Vdc
0–20 mA
min 500 Ohms
max 800 Ohms
NOTE The SE6166 supervises all outputs.
RS sensors
You can wire RS sensors to the SE6166's Rnet port. An Rnet can consist of any of the
following combinations of devices wired in a daisy-chain or star configuration:
• 1 RS Plus, RS Pro, or RS Pro-F
• 1–4 RS Standards
• 1–4 RS Standards, and 1 RS Plus, RS Pro, or RS Pro-F
• Any of the above combinations, plus up to 2 BACviews, but no more than 6 devices
total. See BACviews below.
LogiStats
You can wire a LogiStat or LogiStat Plus to the SE6166's LogiStat port.
NOTES
• The SE6166 does not support the LogiStat Pro.
• A LogiStat or LogiStat Plus wired to the SE6166 cannot be used for local access.
• If you use the Rnet port, you cannot connect a LogiStat sensor to the LogiStat port.
You can wire a BACview
5
or BACview
6
keypad/display unit to the Rnet port of the SE6166
to view or edit some of its property values or its real time clock. See Room sensors above
for Rnet configurations. See the BACview
5
Hardware Setup Guide
(http://accounts.automatedlogic.com) or BACview
6
Hardware Setup Guide
(http://accounts.automatedlogic.com) for installation instructions.
To start up and troubleshoot the SE6166, you can temporarily connect the following items
to its Local Access port:
• The BACview
6
Handheld. See its Technical Instructions
(http://accounts.automatedlogic.com).
• A laptop running the Virtual BACview software. Virtual BACview software simulates the
BACview
6
and is included with WebCTRL v4 or later.
NOTE Before you can use the BACview
5
, BACview
6
, BACview
6
Handheld, or Virtual
BACview with the SE6166, you must create a BACview screen file in ViewBuilder, enter
the screen file name in the controller's
Properties box in SiteBuilder, and then download
the control program to the SE6166.
Analog outputs
Room sensors
BACviews