• No heat sources such as hot air vents or direct sunlight
located near the switch.
• No sources of severe electromagnetic interference located
near the switch.
• No excessive dust in the environment.
• An adequate power source is located within 6 feet (1.83
meters) of the switch. One 15-amp circuit is required for each
power supply.
• At least 2 inches (5.08 centimeters) of clearance on each side
of the switch unit for ventilation.
• Adequate clearance is allotted at the front and rear of the
switch for access to cables.
Table 9: Job aid: Ethernet Routing Switch 5600 Series environmental requirements
Storage temperature –40° to 85°C
Operating temperature : 0° to 50°C (continuous operational.) 0° to
55°C (short term operational)
ESS temperature -5° to 55°C
Operating relative humidity 10 to 90% non-condensing
Storage relative humidity 10 to 95% non-condensing
Operating altitude 13,000 feet above sea level
Storage altitude –1,000 to 40,000 feet above sea level
Cooling Dependent on system requirements
Audible noise 45dB to 55dB nominal
DMT temperature -10° to 60°C
DVT temperature -15° to 65°C
Miscellaneous Operating Considerations
• No heat sources such as hot air vents or
direct sunlight located near the switch.
• No sources of severe electromagnetic
interference located near the switch.
• No excessive dust in the environment.
• An adequate power source is located
within 6 feet (1.83 meters) of the switch.
One 15-amp circuit is required for each
power supply.
Installation preparation