5-9
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
  Handling Precautions
(If [
C0
1
: PV range type] is not RTD or if [
C88
: Special function] is other than 
“5”, [
C89
: Zener barrier adjustment] is not displayed.)
(4)  Press the [enter] key to display a difference in wiring resistance between the A 
and B lines on the lower display.
(5)  Press the [enter] key to store the difference in wiring resistance between the A 
and B lines into this unit as an adjustment value.
(6)  Turn OFF the power to the unit and connect the RTD correctly.
  Handling Precautions
•  The Zener barrier can be used only when the PV range type is 41 to 52 or 
63 to 68.
•  Use a Zener barrier whose resistance is low enough so that the total 
resistance, including wiring resistance, is 85 or less.
•  Adjust the Zener barrier with a resistance difference between the Zener 
barrier and long extension wiring of 20 or less.  If this resistance 
difference is 20 or more, the Zener barrier cannot be adjusted and the 
adjustment value becomes 0.00.
•  Once the Zener barrier has been adjusted, the correction is performed 
with the same adjustment value even though the PV range type is 
changed to other RTD.
•  To return the adjusted value to 0.00, connect PV input terminals 10 and 
11, leaving terminal 12 open, and follow the above steps (2) to (5).
•  Notes for products with S/N 133220_ _ _
• 
Be sure to adjust the unit with wiring No. 1. If the unit is adjusted with 
wiring No. 3, poor accuracy may result.
• 
Use zener barriers recommended by Azbil Corporation. 
If the unit is used with unrecommended zener barriers, accuracy may be 
drastically impaired. Before using such zener barriers, contact the azbil 
Group.