Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
The auto tuning (AT) function is used when the PID constants are set automatically with the control method set at 
“Fixed PID” ([
CtrL
 = 1]).
The AT function can be used when the control method is set to “Fixed PID”.
Starting procedures
(1)  Make sure that the PV input or operation end (heater power, etc.) is 
controllable.
(2)  Using the [
r-
 
-r
] setup of the mode bank, multi-status display, and LED 
monitor, make sure that the operation is in the RUN mode.  If the indicator 
[rdy] is lit and the operation is in the READY mode, change the mode to the 
RUN mode.
(3)  Make sure that the mode indicator [man] is off and the operation is in 
the AUTO mode.  If the indicator [man] is lit and the operation is in the 
MANUAL mode, change the mode to the AUTO mode.
(4)  Set the parameter setting [AT Stop/Start selection] to “AT start ([At] =  
[
At.On
]) ”.
Stopping procedures
The AT function is completed automatically.  To stop the AT function, which is 
running, change the parameter setting [AT Stop/Start selection] to AT stop ([At] 
= [
At.OF
]). Additionally, the AT function is stopped when changing the READY 
mode to the MANUAL mode.
Display during execution of AT 
The decimal point at the 1st digit of the upper display (right end digit) flashes twice 
repeatedly while the AT function is running.  When the AT function is completed 
and the PID constants are changed, this LED goes off.
sp
out
pv
man rsp ev1 ev2 ev3 ot1 ot2
mode
display
enter
para
para enter
display
mode
pv
out
sp
ot2
ot1
ev3
ev2
ev1
rsp
man
Operation during execution of AT
The AT function calculates the PID constants using the limit cycle.
(1)  When the AT function is started, a point, where the SP and PV deviations 
are split to “2:1”, is determined as ON/OFF change point of the manipulated 
variable (MV).
(2)  When the limit cycle is judged as stable, the PID constants are changed and the 
AT function is completed.
5 - 4  Auto Tuning (AT) Function