6-12
Chapter 6.  LIST OF DISPLAYS AND SETTING DATA
6 - 3  List of Setup Setting Displays
The following shows the meanings of the values stated in the “User Level” column:
  0: Basic, Standard, and High function configuration
  1: Standard and High function configuration
  2: High function configuration
Initial value may differ depending on model No.
Setup bank
Bank selection: 
Display Item Contents
Initial 
value
User 
level
Notes
PV input range type
Range of thermocouple: 1 to 26 
Range of RTD: 41 to 68 
Range of DC voltage and DC 
current: 81 to 84, 86 to 90
88 0
For details, refer to the PV 
Input Range Table (on page 
5-2).
Temperature unit
0: Celsius (°C) 
1: Fahrenheit (°F)
0 0
Displayed when the PV input range 
type is thermocouple or RTD.
Cold junction 
compensation (T/C)
0:  Cold junction compensation (T/C) 
is performed (internal).
1:  Cold junction compensation (T/C) 
is not performed (external).
0 2
Displayed when the PV input 
range type is thermocouple.
Decimal point 
position
0: No decimal point 
1: 1 digit after decimal point 
2: 2 digits after decimal point 
3: 3 digits after decimal point 
(Range with decimal point of 
thermocouple/RTD: 0 to 1)
0 0
Displayed when the PV input 
type is DC voltage/DC current 
or thermocouple/RTD having 
the range with the decimal 
point.
PV range low limit
When the PV input range type is 
thermocouple or RTD, the input 
range low limit selected with the PV 
input range type (
C0
 
1
) is displayed, 
but the setting is disabled. 
When the PV input range type is DC 
voltage/DC current, a value ranging 
from –1999 to +9999 is set.
0 0
PV range high limit
When the PV input range type is 
thermocouple or RTD, the input 
range high limit selected with the PV 
input range type (
C0
 
1
) is displayed, 
but the setting is disabled.
 
When the PV input type is DC 
voltage/DC current, a value ranging 
from –1999 to +9999 is set.
1000 0
SP low limit
PV range low limit to PV range high 
limit
0 1
SP high limit
1000 1
PV square root 
extraction dropout
0.0 to 100.0 
(PV square root extraction is not 
performed when set at “0.0”.)
0.0 2
Displayed when the PV input 
range type is DC voltage/DC 
current.
RSP input range type 0: 4 to 20 mA 
1: 0 to 20 mA 
2: 0 to 5 V 
3: 1 to 5 V 
4: 0 to 10 V
0 0
Displayed when the model 
provides the RSP input.
RSP range low limit -1999 to +9999 U
0 0
RSP range high limit -1999 to +9999 U
1000 0
PID calculation 
adjustment function
0: Enabled 
1: Disabled
0 2
Normally, the PV filter is used 
with an initial value. 
If ROM version 1 in the 
instrument information bank  
(
i
d02
) is 2.26 or earlier, this 
item cannot be displayed.
Control action 
(Direct/Reverse)
0: Reverse action (Heat) 
1: Direct action (Cool)
0 0
Displayed when the heat/cool 
control is not used (
C26
=0).