10-1
Chapter 10.
MAINTENANCE AND TROUBLESHOOTING
Maintenance
Cleaning
When removing dirt from the instrument, wipe it off with a soft cloth rag. At this
time, do not use any organic solvent, such as paint thinner or benzine.
Part replacement
Do not replace any parts of this unit.
Fuse replacement
When replacing the fuse connected to the electric wiring, always use the specified
standard fuse.
Standard IEC127
Shut-down speed Slow-action type (T)
Rated voltage 250 V AC
Rated current 0.5 A