D-4
Setup of PV input range type
1
Press [display] once 
to get the operation 
display.
If the sensor has not been 
wired or is disconnected, 
an alarm for abnormal PV 
input (any one from 
AL0
 
1
 
to 
AL
 
1
 
1
)  may appear on 
the upper display.
2
Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 
MOde
 flashes on the 
upper display.
3
Press [ ] or [ ] repeat-
edly, and 
Stup
 flashes 
on the upper display.
4
Press [enter]. 
The current set value  
for 
C0
 
1
 (PV input 
range type) is 
displayed.
5
Press [enter]. 
The rightmost digit on the lower display flashes and its value 
can be changed. 
Press [<], [ ] or [ ] to change to the desired sensor type in the 
PV input range list. 
Then press [enter] to finalize your selection. 
If the number is flashing, the [enter] key has not yet been 
pressed, and the setting has not yet been saved.
Setup of event operation type
In this example, the event 1 operation type is set to deviation high 
limit.
1
Press [display] once 
to get the operation 
display.
2
Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 
MOde
 flashes on the 
upper display.
3
Press [ ] or [ ] repeat-
edly to get 
evCf
 
flashing on the upper 
display.
4
Press [enter] to get 
e
1.c
 
1
 on the upper 
display and 
0
 is dis-
played on the lower 
display.
0
 on the lower display indi-
cates that the event opera-
tion type is set to "none."
5
When [enter] is 
pressed, the rightmost 
digit on the lower dis-
play flashes. 
Press [ ] or [ ] to get 
4
 
flashing on the display.
4
 on the lower display 
indicates that the event 
operation type is set for 
deviation high limit.
6
Press [enter], and the 
displayed value 
4
 
on the lower display 
changes from flashing 
to continuously lit and 
the displayed value 
is set.
Similarly, use 
e2.C
 
1
 to set the event 2 operation type, and use 
e3.C
1
 for event 3.
Red letters : Items before operation
Blue letters : Items during operation
Execution of auto tuning (AT)
AT forces ON/OFF of the MV a number of times (a limit cycle) to cal-
culate PID values. 
Check that this operation does not create any problems for the as-
sociated equipment before executing AT.
1
Press [display] once 
to get the operation 
display.
2
Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 
MOde
 flashes on the 
upper display.
3
Press [enter] or [<] 
to get 
A--M
 on the 
upper display and 
autO
 on the lower 
display.
If the control method is 
ON/OFF control and if Bit 
3 (AT stop/start display) of 
the mode display setting 
(
C73
) is set to "disabled: 0," 
nothing is displayed.
4
Press [ ] as needed 
until 
At
 and 
at.Of
 
appear on the upper 
and lower displays 
respectively.
5
When [enter] is 
pressed, 
at.Of
 flashes 
on the lower display.
The display flashes only 
in RUN and AUTO modes, 
and only if there is no PV 
problem. 
Also, if DI is set to "AT stop/
start", the display does not 
flash and the setting can-
not be changed.
6
Press [ ] or [ ] once, 
and 
at.Of
 flashes on 
the lower display.
7
If [enter] is pressed, 
at.ON
 remains steadily lit and AT begins. 
During AT, the rightmost decimal point flashes twice repeat-
edly. 
When AT is done, the light goes off and the new PID values 
go into effect.
During the AT process, if the mode is changed to READY or MANUAL, if PV 
input is faulty, or if a power failure occurs, AT stops automatically without 
changing the PID values. 
AT can also be stopped by changing the setting from 
At.ON
 to 
At.OF
 (return 
to step 4 above).
Setup of SP value
1
Press [display] re-
peatedly so that the 
orange SP indicator 
lights up on the lower 
display. 
The operation display 
now shows the SP.
2
If [enter] is pressed, 
the rightmost digit 
on the lower display 
flashes and numerical 
value can be changed.
3
Press [<], [ ] or [ ] to 
change to the desired 
SP value. 
The flashing of the 
number indicates that 
the setting has not yet 
been finalized.
If an SP limit is in effect, the 
numerical value cannot be 
changed to a value above 
the limit. The SP limit must 
be changed first.
4
If [enter] is pressed, 
the displayed value 
is set and the display 
changes from flashing 
to continuously lit.
If the [display] key is 
pressed without pressing 
[enter] key, the status re-
turns to that of step 1.
Operation examples