5-10
Chapter 5.  DETAILED DESCRIPTION OF EACH FUNCTION
It is possible to set the AUTO/MANUAL mode selection, RUN/READY mode selection, LSP/RSP mode 
selection, Auto Tuning (AT) stop/start selection, release all digital output (DO) latches, and OFF/ON selection of 
communication digital input 1 (communication DI 1).
AUTO/MANUAL mode
The AUTO/MANUAL mode selection can be set.
Item (Bank) Display Contents Initial value User level
AUTO/MANUAL 
mode selection 
(Mode bank)
AUtO
:  AUTO mode [Communication value is "0".] 
MAn
:  MANUAL mode [Communication value is "1".]
AUtO
Basic, 
Standard, 
High function
•  When the AUTO/MANUAL mode is changed, the display is automatically 
returned to the operation display.
•  If the operation type of internal contacts 1 to 5 is set at “AUTO/MANUAL”,  
[
A--M
: AUTO/MANUAL mode selection] can be displayed, but the setting 
cannot be configured.
•  When [
CtrL
: Control method] is set at "0" (ON/OFF control), [
A--M
: AUTO/
MANUAL mode selection] cannot be displayed and set.
•  When [
bit
 
0
: AUTO/MANUAL display] of [
C73
: MODE display setup] is set at "0" 
(no display), [
A--M
: AUTO/MANUAL mode selection] cannot be displayed and 
set.
RUN/READY mode
The RUN/READY mode selection can be set.
Item (Bank) Display Contents Initial value User level
RUN/READY mode 
selection 
(Mode bank)
rUn
: RUN mode [Communication value is "0".]
rdy
:  READY mode [Communication value is "1".]
rUn
Basic, 
Standard, 
High function
•  If the operation type of internal contacts 1 to 5 is set at “RUN/READY”, [
r--r
: 
RUN/READY] can be displayed, but the setting cannot be configured.
•  When [
bit
 
1
: RUN/READY display] of [
C73
: MODE display setup] is set at "0" (no 
display), [
r--r
: RUN/READY mode selection] cannot be displayed and set.
LSP/RSP mode
The LSP/RSP mode selection can be set.
Item (Bank) Display Contents Initial value User level
LSP/RSP mode 
selection 
(Mode bank)
LSP
: LSP mode [Communication value is "0".]
RSP
:  RSP mode [Communication value is "1".]
LSP
Basic, 
Standard, 
High function
•  If the operation type of internal contacts 1 to 5 is set at “LSP/RSP”, [
L--r
: LSP/
RSP mode selection] can be displayed, but the setting cannot be configured.
•  When [
bit
 
2
: LSP/RSP display] of [
C73
: MODE display setup] is set at "0" (no 
display), [
L--r
: LSP/RSP mode selection] cannot be displayed and set.
•  If the model does not have the RSP mode, [
L--r
: LSP/RSP mode selection] cannot 
be displayed and set.
5 - 2  Mode