6-1
Chapter 6.  LIST OF DISPLAYS AND SETTING DATA
6 - 1  List of Operation Displays
The following shows the meanings of the values stated in the “User Level” column:
  0: Basic, Standard, and High function configuration
  1: Standard and High function configuration
  2: High function configuration
Operation displays
Display Item Contents
Initial 
value
User 
level
Notes
Upper display: PV
Lower display: SP
SP (Target value)
SP low limit (
C07
) to SP high limit 
(
C08
)
0
0
Whether or not this item is 
displayed is selected by the 
PV/SP display setup (
C74
).
(Display 
example) 
Lower display: 
LSP
LSP No. 
(1st digit: Value at 
the right end digit)
1 to LSP system group (
C30
, Max. 8)
1 0
Displayed when LSP system 
group (
C30
) is “2” or more. 
The lower display shows the 
LSP set value corresponding 
to the LSP group number. 
Whether or not this item is 
displayed is selected by the 
PV/SP display setup (
C74
).
(Display 
example) 
Lower display: 
Step remain time
Step operation 
remaining time
Setting is disabled. 
Upper display shows the step No. (1 
to 8), and distinction among the soak, 
up ramp, and down ramp on the 
right of “
St.
”.  Lower display shows 
the soak remain time or ramp remain 
time.
1
0
Regardless of the soak or ramp 
operation, the remain time 
is displayed in step time unit 
(setup 
C33
).  When the unit is 
1s, “min.s” is displayed.  When 
the unit is 1min, “h.min” is 
displayed.
Upper display: 
PV 
Lower display: 
MV
MV (Manipulated 
Variable)
-10.0 to +110.0 % 
Setting is disabled in AUTO mode. 
(Numeric value does not flash.) 
Setting is enabled in MANUAL 
mode. (Numeric value flashes.)
— 0
In the ON/OFF control (
CtrL
 
= 0), "100.0" is displayed at 
ON and "0.0" is displayed at 
OFF. Whether or not this item 
is displayed is selected by the 
MV display setup (
C75
).
Heat MV 
(Manipulated 
Variable)
Setting is disabled. 
-10.0 to +110.0 %
— 0
This item is displayed when 
using the Heat/Cool control 
(
C26
 = 1). 
Whether or not this item is 
displayed is selected by the 
MV display setup (
C75
).
Cool MV 
(Manipulated 
Variable)
— 0
MFB (Motor opening 
feedback value)
Setting is disabled. 
-10.0 to +110.0 % 
Flashing when the value is 0.0 to 
100.0% during estimate.
— 0
Displayed during execution of 
AT. (The display is continued 
even after completion of AT.) 
Whether or not this item is 
displayed is selected by the 
MV display setup (
C75
).
Upper display: 
PV
(Display 
example)
AT progress display 
(1st digit = Numeric 
value at right end 
digit)
Setting is disabled. 
Lower display shows the AT 
progress value on the right of “
At
”.  
1 - :  During execution of AT (Value is 
decreased.)
0: Completion of AT
— 0
Displayed during execution of 
AT. (The display is continued 
even after completion of AT.) 
Whether or not this item is 
displayed is selected by the 
MV display setup (
C75
).
CT (Current trans-
former) current 
value 1
Setting is disabled.
— 0
Displayed when the optional 
model has two current 
transformer points. 
Whether or not this item is 
displayed is selected by the 
CT input current value display 
setup (
C78
).
CT (Current trans-
former) current value 2
Setting is disabled.
— 0
Internal Event 1  
main setting
The allowable setting range may 
vary depending on the operation 
type of the internal event. 
-1999 to +9999 U: Set value is other 
than the following values: 
0 to 9999 U: Set value is an absolute 
value. 
-199.9 to +999.9 %: Set value is MV.
0 0
Setting required by the 
operation type of the internal 
event is displayed. 
Whether or not this item is 
displayed is selected by the 
Event setting value display 
setup (
C76
).
Internal Event 1  
sub-setting
0 0