Measure Menu
Measure
Flow Unit
U
This parameter establishes the unit of measure for the flow rate and full scale flow. Changing this
parameter readjusts the full scale flow parameter. For example, changing from GPM to GPS would
change the full scale flow from 60 gal/min to 1 gal/s.
Display Flow Unit Display Flow Unit
L/s Liters/Second gal/s Gallons/Sec.
L/min Liters/Minute gal/min Gallons/Min.
L/h Liters/Hour gal/h Gallons/Hour
m
3
/s Cubic Meters/Sec. MG/d MillionGallons/Day
m
3
/min Cubic Meters/Min. IG/s ImperialGallons/Sec.
m
3
/h Cubic Meters/Hour IG/min ImperialGallons/Min.
ft
3
/s Cubic Feet/Sec. IG/h ImperialGallons/Hour
ft
3
/m Cubic Feet/Min. oz/min Ounce/Min
ft
3
/h Cubic Feet/Hour. bbl/min Barrel/Min
Totalizer Unit
U
This parameter establishes the units of measure for the totalizers.
Display Totalizer Unit
L Liters
hL Hectoliter
m
3
Cubic Meters
ft
3
Cubic Feet
gal U.S. Gallons
MG Million Gallons
IG Imperial Gallons
bbl Barrel
oz Fluid Ounces
ac/ft Acre per foot
Full Scale Flow
S
This parameter sets the maximum flow that the system is expected to measure. This parameter has
influence on other system parameters, which include:
Low Flow Cutoff – Changes to full scale flow affect the measuring cut-off threshold of the meter
Alarm Outputs – Changes to full scale flow adjusts the thresholds for generating setpoint alarms
Pulse Outputs – Changes to full scale flow adjusts the pulse frequency and duty cycle
Change the full scale flow based on the meter size and the applications requirements. Verify that the
full scale flow falls within the meter’s suggested flow range limits.
Flow Range: 0.1…32.8 ft/s (0.03…10 m/s)
The full scale flow is valid for both flow directions.
OTE:N If the flow rate exceeds the full scale setting of more than 100%, a FLOW_OVERLOAD_
WARNING message indicates that the configured full scale range has been exceeded.
However, the meter will continue to measure. This will affect the latency of the pulse outputs
and possibly cause overflow.
User Manual
Page 23 September 2013
| sales@mvandc.com | Phone: 877.566.3837 | Fax: 925.407.2903

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Badger Meter M5000 and is the answer not in the manual?

Badger Meter M5000 Specifications

General IconGeneral
BrandBadger Meter
ModelM5000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals