Appendix F. Foundation Fieldbus Communication
108 PanaFlow™ XMT1000 User’s Manual
F.4.2 Password
A password must be entered to change XMT1000 system parameters. This can be done using Foundation Fieldbus.
There are different levels of security for different Passwords (Admin or Operator). Please see the standard manual for
more detail on password levels. Figure 70 below shows the password fields in the XMT1000 Resource Block.
Figure 70: Password Fields in XMT1000 Resource Block
To Enter configuration mode, complete the following steps:
1. Select the Resource Block > Others tab.
2. Select SYSTEM_OPT_TYPE and set to Option FI.
3. Select SYSTEM_REQ_LEVEL and set to Admin or Operator.
4. Enter the Admin or Operator password into the SYSTEM_REQ_PASS field.
5. Select Cancel from the SYSTEM_REQ_CMD drop down box.
6. Select Login from the SYSTEM_REQ_CMD drop down box.
7. Click on the Write Changes button.
8. Verify that S1:In Config Mode appears on XMT1000 display. You should now be able to edit fields with Admin priv-
ileges.
Attention: Before entering a password, make sure the XMIT_TB transducer block is in active mode.