10
4 Technical data
PROFINET
4.5.
PROFINET port
1 x 10Base-/100Base-Tx
Connection for PROFINET port
M12, D-coded, female
Cable types in accordance with
IEE 802.3
Shielded, twisted pair min. STP CAT 5/ STP CAT 5e
Data transmission rate
10/100 Mbit/s
Max. cable length
100 m
Flow control
Half-duplex/full-duplex (IEEE 802.33x pause)
Function
4.6.
indicators
Module status
LED
Display
Function
US
Green
Input voltage OK
Red, flashing
Input voltage low (< 18 V)
UA
Green
Output voltage OK
Red, flashing
Output voltage low (< 18 V)
Red
No output voltage present (< 11V)
SF
off
No error
Red
Watchdog timeout; channel, general or advanced
diagnosis present; system error
Red, flashing
Service DCP signal started via bus
BF
off
No error
Red
Low speed of physical link; or no physical link
Red, flashing
No data exchange or no configuration
100
off
Transmission rate: 10 Mbit/s
Yellow
Transmission rate: 100 Mbit/s
LK
Green
Data transfer
Port-Leds
Status-Leds