Balluff Network Interface ProfiNet™
www.balluff.com
19
5 Integration
Module settings
Global diagnostics:
This function can be used to permit / suppress all diagnostics messages of the module.
(optical diagnostics signals and diagnostics in configured diagnostics modules
are not affected)
Sensor supply undervoltage:
This function can be used to permit / suppress the diagnostics message Sensor supply
undervoltage. (Optical diagnostics and diagnostics in configured diagnostics modules are
not affected)
Actuator supply undervoltage:
This function can be used to permit / suppress the diagnostics message Actuator supply
undervoltage. (optical diagnostics signals and diagnostics in configured diagnostics modules
are not affected)
Sensor short circuit at output:
With this function, the diagnostic message sensor short circuit is allowed to output of the
module / suppressed to the output of the module.
(Optical diagnostics and diagnostics in configured diagnostics modules are not affected.)
This function is valid only for channels / pins that are configured as outputs.
As inputs configured channels / pins are not affected.
Port functions
The function for every individual port pin can be defined here:
Make contact = input as normally open contact
Break contact = input as normally closed contact
Output = output function
IO-Link= IO-Link function
Make contact after configuration = SIO mode; one IO-Link device can be configured via
IO-Link and then moved to an SIO mode in which the
IO-Link port pin functions as a simple switch input
Break contact after configuration = SIO mode, as with make contact after configuration, but
as break contact input
Safe state
This function is a supplement to an output configuration of the respective port pin.
For each port pin, a safe status can be predefined which is to be assumed in the event of
a loss of bus communication.
Functions in
5.2.
module properties
Description of the functions in module properties