Balluff Network Interface ProfiNet™
www.balluff.com
13
5 Integration
Configuration of
the header
module
Double-click on the header module to open its properties.
Click on the "Parameter" tab to open a menu selection for defining the
port functions and diagnostic functions.
Note
IO-Link configuration:
For modules with an firmware version 2.3 or higher, the configuration of pin 4 as
IO-Link port is not necessary anymore. The port is automatically configured to
IO-Link, when an IO-Link process data module is used in the hardware
configuration. Therefore the option to set pin 4 to IO-Link is removed in the new
GSDML files.
If the connected IO-Link device makes outputs available, pin 2 must be configured
to output on the corresponding port.
Standard input and output:
For each port, the function (N.C., N.O., diagnostic input (pin 2)) can be arbitrarily
selected for each port at pin 2 and pin 4.