EasyManuals Logo

Balluff BNI00E7 User Manual

Balluff BNI00E7
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
www.balluff.com
31
8 Parameter Processing
Error codes for
Processing
parameter
If while transmitting parameters errors occur in the Engineering Tool:
Error code
Description
0xXXXXCEE0
SLMP_ERROR_UNDER_EXECUTION
0xXXXXCEE1
SLMP_ERROR_REQUEST_DATA_SIZE
0xXXXXCEE2
SLMP_ERROR_RESPONSE_DATA_SIZE
0xXXXXCF20
SLMP_ERROR_CAN_NOT_COMMUNICATION_SETTING
0xXXXXCF30
SLMP_ERROR_NO_EXIST_PARAMETER_ID
0xXXXXC061
SLMP_ERROR_WRONG_DATA
0xXXXXCF31
SLMP_ERROR_CAN_NOT_PARAMETER_SET
SLMP_ERROR_RESPONSE_DATA_SIZE:
SLMP_ERROR_REQUEST_DATA_SIZE:
SLMP_ERROR_CAN_NOT_COMMUNICATION_SETTING:
SLMP_ERROR_NO_EXIST_PARAMETER_ID:
There may be a newer or older version of the CSP_ file compared with the firmware version.
SLMP_ERROR_UNDER_EXECUTION:
Another SLMP telegram is currently under execution
SLMP_ERROR_CAN_NOT_PARAMETER_SET:
It is currently not possible to write parameters, since the start conditions are not met.
Cause: parameters were written simultaneously from more than one Engineering Tool,
or there was an error in the Engineering Tool
SLMP_ERROR_WRONG_DATA:
The received data are incorrect, such as wrong port number. For example a value is read/
written for port 9 even though no such port exists.