Program Code 1 ÞÞ: Voices
When you enter Program Code 1, you will hear the following prompt:
B1290: Enter Voice Code
YOU:
1** Record Site ID and alarm messages
2** Record relay messages
3** Erase all messages
** Exit to Enter Program Code prompt
1ÞÞ: Record Alarm Voices (includes Site ID)
Record the voice messages associated with the unit (site ID) and each indi
-
vidual alarm point. These are the messages which will be announced over
the radio or telephone whenever the alarm is present.
B1290: Site is Ajax Compressor Station
YOU:
2** Record
#** Quit
** Enter/Next
Default: empty
IfthemessageisOK,continuebyhittingEnter. Ifyouwouldliketorecorda
new message, enter 2ÞÞ to record. As soon as you hit the second asterisk
of the Enter code, the B1290 will prompt you to record a voice message.
When you stop speaking, the B1290 will immediately play back the mes
-
sage that you recorded. Pauses between words may cause the recording to
terminate. Repeat as many times as you need until the voice message
sounds acceptable. Thenhit Enter(ÞÞ) to proceed,or #ÞÞ to exit back to
the Enter Voice Code prompt.
Entering Next advances to the alarm message section and the first alarm
message will be spoken
B1290: Alarm One is
YOU:
2** Record
#** Quit
** Enter/Next
If you enter messages for all eight alarms, the B1290 will automatically exit
to the Enter Voice Code prompt.
Default: empty
29 Program Codes