B1290: Enter Configuration Code
YOU:
2** Select Using Directory
B1290: Alarm One is Directory...
YOU:
1** Select Directory A
B1290: Alarm One is Directory A
YOU:
** Next
B1290: Alarm Two is Directory...
YOU:
1** Select Directory A
B1290: Alarm Two is Directory A
YOU:
** Next
B1290: Alarm Three is Directory A
YOU:
2** Select Directory B
B1290: Alarm Three is Directory B
B1290: Alarm Four is Directory A
YOU:
2** Select Directory B
B1290: Alarm Four is Directory B
YOU:
#** Quit
The B1290 is now programmed to dial Directory A when alarms 1 or 2 oc
-
cur, and Directory B when alarms 3 or 4 occur.
Example 4: Actuating Relays
In this example, when you receive the alarm “High Pressure” from the
B1290,you would liketobe abletooperate abypassvalve forupto ten min
-
utes. Thevalvecanbecontrolledbyone of therelays on theB1290 using Re
-
lay On and Relay Off codes.
B1290: Enter Program Code
YOU:
1** Select Voices
B1290: Enter Voice Code
YOU:
2** Select Relay Voices
B1290: Relay One is...
YOU:
2** Change
B1290: beep-beep
55 Programming Examples