9492600990 19-5
DECS-150 BESTlogic™Plus
Name
Description
Symbol
GCC Freq High
Timing
True when the controlled generator’s
frequency is in the high frequency region for
GCC and the timer is active.
GCC Freq Low
Timing
True when the controlled generator’s
frequency is in the low frequency region for
GCC and the timer is active.
GCC Out of
Range Timing
True when the controlled generator’s
frequency or voltage is in the Out of Range
region for GCC and the timer is active.
GCC Timing for
Disconnect
True when any of the GCC timers is active.
GCC Timing for
Reconnect
True when the GCC reconnect timer is
active.
GCC Voltage High
Timing
True when the controlled generator’s voltage
is in the high voltage region for GCC and the
timer is active.
GCC Voltage Low
Timing
True when the controlled generator’s voltage
is in the low voltage region for GCC and the
timer is active.
Generator/Motor
Below 10 Hz
Pickup
True when the machine is operating below
10 Hz and the element is timing towards a
trip.
Generator/Motor
10 Hz Trip
True when the machine is operating below
10 Hz for 100 ms.
Grid Code
Enabled
True when the Grid Code Connectivity
function is enabled.
Hardware
Shutdown
True when a user-configured protection
element or limiter causes a forced shutdown.
Internal Tracking
Active
True when internal tracking is running.
KW Threshold
True when kW output is below the standard
(non-Grid Code) PF Active Power Level.
LFSM Active
True when Limited Frequency Sensitive
Mode (LFSM) is active.
LFSM Enable
True when LFSM is enabled.
LFSM Normal
Operation
True when LFSM is enabled and grid
frequency is within the dead band.
LFSM
Overfrequency
Active
True when LFSM is enabled and grid
frequency is greater than the LFSM-O Dead
Band setting value.