19-6 9492600990
BESTlogic™Plus DECS-150
Active
True when LFSM is enabled and the Grid
Recovery timer is active.
Underfrequency
Active
True when LFSM is enabled and grid
frequency is less than the LFSM-U Dead
Band setting value.
Pickup
True when the Loss of Sensing pickup
threshold is exceeded and the element is
Trip
True when the Loss of Sensing pickup
threshold is exceeded for the duration of the
True when Low Voltage Ride Through
(LVRT) mode is active.
Active
True when LVRT Bridge mode is active.
Enable
True when LVRT Bridge mode is enabled.
True when LVRT mode is enabled.
Comm Fail
True when the LVRT Adjust Source setting is
set to Modbus and the Remote Control
Failure Timer has expired.
Comm Active
True when the Remote Control Failure Timer
is active. The Remote Control Failure Timer
is always active and resets frequently, during
good communications.
Comm Fail
True when the Remote Control Failure Timer
has expired for any communication protocol
(defined by the Adjust Source setting).
Mode
True when LVRT remote communication has
failed.
Active
True when the unit is in Manual mode (FCR).
Share Active
True when network load sharing is active.
Share Config
True when the unit’s configuration does not
match the configuration of the other units
with load sharing enabled.
Share ID Missing
True when any of the load sharing enabled
units are not detected on the network.
Share Receiving
True when data is being received from a
specific unit on the load share network.