19-6 9492600990
BESTlogic™Plus DECS-150
Name
Description
Symbol
LFSM Recovery
Active
True when LFSM is enabled and the Grid
Recovery timer is active.
LFSM
Underfrequency
Active
True when LFSM is enabled and grid
frequency is less than the LFSM-U Dead
Band setting value.
Loss of Sensing
Pickup
True when the Loss of Sensing pickup
threshold is exceeded and the element is
timing towards a trip.
Loss of Sensing
Trip
True when the Loss of Sensing pickup
threshold is exceeded for the duration of the
time delay.
LVRT Active
True when Low Voltage Ride Through
(LVRT) mode is active.
LVRT Bridge
Active
True when LVRT Bridge mode is active.
LVRT Bridge
Enable
True when LVRT Bridge mode is enabled.
LVRT Enable
True when LVRT mode is enabled.
LVRT Modbus
Comm Fail
True when the LVRT Adjust Source setting is
set to Modbus and the Remote Control
Failure Timer has expired.
LVRT Remote
Comm Active
True when the Remote Control Failure Timer
is active. The Remote Control Failure Timer
is always active and resets frequently, during
good communications.
LVRT Remote
Comm Fail
True when the Remote Control Failure Timer
has expired for any communication protocol
(defined by the Adjust Source setting).
LVRT Remote Fail
Mode
True when LVRT remote communication has
failed.
Manual Mode
Active
True when the unit is in Manual mode (FCR).
Network Load
Share Active
True when network load sharing is active.
Network Load
Share Config
Mismatch
True when the unit’s configuration does not
match the configuration of the other units
with load sharing enabled.
Network Load
Share ID Missing
True when any of the load sharing enabled
units are not detected on the network.
Network Load
Share Receiving
ID 1-16
True when data is being received from a
specific unit on the load share network.