DECS-150 BESTlogicâ„¢Plus
Share Data
True when Network Load Sharing is enabled
but there is no data being received from
other network load sharing devices.
Share Status 1-4
This element functions in conjunction with
the Network Load Share Broadcast elements
on all units on the network. True when the
corresponding Network Load Share
Broadcast element input is true on another
True when Null Balance is achieved in both
external and internal tracking.
True when the Overexcitation Limiter is
active.
Active
True when the unit is in PF mode.
Alarm
True when power input voltage is below
normal operating range.
Active
True when any pre-position is active.
Active
True when Pre-Position x is active.
(Optional)
True when the power system stabilizer (PSS)
is turned on and running.
Unbalanced
True when the phase current is unbalanced
and the PSS is active.
Threshold
True when the input power is below the
Power Level threshold and the PSS is active.
Group (Optional)
True when the PSS is using secondary
settings.
(Optional)
True when the frequency is out of range for a
length of time calculated internally by the
DECS-150 and the PSS is active.
(Optional)
True when the power system stabilizer test
signal (Frequency Response) is active.
(Optional)
True when the calculated terminal voltage
upper or lower limit is reached and the PSS
Unbalanced
True when the phase voltage is unbalanced
and the PSS is active.
True when the Stator Current Limiter is
active.
Limit
True when the active modes setpoint is at
the lower limit.