DECS-150 Modbus
®
Communication
Group
Name
Register
Type
Bytes
R/W
Unit
Range
DECS Control
System Option Fine Adjust Band
2730
Float
4
R W
Percent
0–30
DECS Control
System Option Underfrequency Slope
2732
Float
4
R W
n/a
0–3
DECS Control
System Option PF to Droop kW Threshold
2734
Float
4
R W
Percent
0–30
DECS Control
Startup Primary Soft-start Bias
2736
Float
4
R W
Percent
0–90
DECS Control
Startup Primary Soft-start Time
2738
Float
4
R W
Second
1–7200
DECS Control
Startup Secondary Soft-start Bias
2740
Float
4
R W
Percent
0–90
DECS Control
Startup Secondary Soft-start Time
2742
Float
4
R W
Second
1–7200
DECS Control
System Input COM Port Preposition 3
Enabled
2744
Uint32
4
R W
n/a
NOT SET=0 SET=1
DECS Control
System Option Underfrequency Hz 2
2746
Float
4
R W
Hertz
1–75
DECS Control
System Option Underfrequency Slope 2
2748
Float
4
R W
n/a
0–3
Auto Save
Enable
2750
Uint32
4
R W
n/a
Disabled=0 Enabled=1
Modbus
Auto Save
2752
Uint16
2
R W
n/a
Off=0 On=1
System Config
Tracking Comms Loss Alarm Enable
2753
Uint32
4
R W
n/a
Disabled=0 Enabled=1
System Config
Tracking Comms Loss Activation Delay
2755
Uint32
4
R W
Second
2–60
Protection Settings
Table 25-12. Protection Settings Group Parameters
Group
Name
Register
Type
Bytes
R/W
Unit
Range
Programmable Alarms
Programmable
Alarm 1 Delay
3100
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 2 Delay
3102
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 3 Delay
3104
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 4 Delay
3106
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 5 Delay
3108
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 6 Delay
3110
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 7 Delay
3112
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 8 Delay
3114
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 9 Delay
3116
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 10 Delay
3118
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 11 Delay
3120
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 12 Delay
3122
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 13 Delay
3124
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 14 Delay
3126
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 15 Delay
3128
Float
4
R W
Second
0–300
Programmable Alarms
Programmable
Alarm 16 Delay
3130
Float
4
R W
Second
0–300
Field Overvoltage
Primary Mode
3132
Uint32
4
R W
n/a
Disabled=0 Enabled=1
Field Overvoltage
Primary Pickup
3134
Float
4
R W
V
Disabled=0, 1–300
Field Overvoltage
Primary Time Delay
3136
Float
4
R W
Millisecond
Instantaneous=0, 0–30000
Field Overvoltage
Secondary Mode
3138
Uint32
4
R W
n/a
Disabled=0 Enabled=1
Field Overvoltage
Secondary Pickup
3140
Float
4
R W
V
Disabled=0, 1 - 300