Parameter
V-Controller (BUS 6 VC) 49
Baumüller Nürnberg Electronic GmbH & Co. KG 5.03047.01
Uzk control is disabled
main contactor is switched off (BUC contact between X1:6/X1:7 is opened)
relay "ready for use" is OFF (relay is fallen off - BUC is not ready)
Uzk control is disabled
main contactor is switched off (BUC contact between X1:6/X1:7 is opened)
drive controller expects the error acknowledgement (see X26:17, terminal diagram V-controller)
Unit control states:
content of control and state word
switching state of the "ready for use" relay
E
FAULT REACTION ACTIVE
F
FAULT
Unit control
state
P120 M control word P121 M state word Switching state
"ready for use"
relay
0 initialization phase initialization phase OFF
1 0x000A 0x0060 OFF
2 0x000E 0x0021 OFF
9 0x000E 0x0021 OFF
3 0x000E 0x0033 OFF
4 0x000F 0x0437 ON
E 0x000E 0x0028 OFF
F 0x000E 0x0028 OFF