Parameter
62 V-Controller (BUS 6 VC)
5.03047.01 Baumüller Nürnberg Electronic GmbH & Co. KG
Parameter description
P190 DSM command
This command instructs the data set management to load, to save and to delete an existing
data set.
P191 DSM state
P192 DSM message
If a message occurs during the implementation of a command, it is displayed in this parame-
ter.
NOTE
This parameter is independent of the parameter M communication source (P126) always
changeable.
Command Meaning
0 reset of data set management
The parameter P191 till P195 are set automatically to 0.
5 save data set from user memory to EEPROM
6 load data set from EEPROM to user memory
7 delete EEPROM data set
8 input password
Bit no. Meaning
0 ... 2 000 : STOP Data set management is ready for a command or for changing data
sets.
001 : RUN Data set management is processing a command.
011 : STAND_BY Data set management has finished a command.
3 1 : An error has occurred in the data set management.
Error code see P124, M error code and P192, DSM message
4 ... 15 reserved
Bit no. Meaning
0 1: undefined command
1 1: data set not available
2 1: wrong check sum
3 1: parameter not changeable
4 reserved
5 1: memory full
6 1: error in configuration list
7 1: undefined parameter format