15. TROUBLESHOOTING SERVICE FAULTS
 and a number (fault code). For a complete list of faults, see the

If appears on the display the fault must be RESET by the user.
 for 2 seconds. If faults are displayed frequently, call the Authorised Service Centre.
Description of fault Service action
09
Gas valve connection error

electronic board.
10
External probe sensor faulty Check the sensor (*).
12
 
13
 See the actions indicated in E12
15
Gas valve control error

electronic board. If necessary, replace the electronic board.
18
 
19
 
20

Check the sensor (**).


28
NTC fumes sensor faulty
Check the fumes NTC probe (***).


40
NTC return sensor faulty See the actions indicated in E20
50


See the actions indicated in E20
53
Fumes outlet obstructed
Check that the drainage pipe is free from obstructions.

seconds.
55
Electronic board not calibrated
Activate the automatic calibration function described in the
spare parts instructions sheet.
83…87



board or RF link.
92
Fumes fault during calibration (probable fumes recirculation)
Check for any recirculation of fumes.
Activate the automatic calibration function described in
the paragraph YEARLY MAINTENANCE – REPLACING
COMPONENTS.
109
Air in boiler circuit (temporary fault)



110
Safety thermostat tripped due to overtemperature (pump
probably blocked or air in heating circuit).



Check that the limit thermostat is undamaged and replace it if
necessary

117
Pressure in hydraulic circuit too high (> 2.7 bar)
Check that the pressure in the system is correct
See the FILLING THE SYSTEM section.
118


the FILLING THE SYSTEM section).

125
No circulation safety trip.
(control performed via a temperature sensor)
See the actions indicated in E109
128


and correctly positioned (see the ANNUAL SERVICING -
POSITIONING THE ELECTRODES section).


See the actions indicated in E92
129


and correctly positioned (see the ANNUAL SERVICING -
POSITIONING THE ELECTRODES section).


Check for any recirculation of fumes.
130
Fumes NTC tripped due to overtemperature


Check the fumes NTC probe (***).