20 Screen page "Position" (P)
Cycle time of the position controller: 250 µs
Subscreens
Position Data
Opens the screen page "Position Data"
Homing
Opens the screen page "Homing"
Gearing
Opens the screen page "Gearing"
Ff Factor
ASCII: GPFFV
Default: 1 valid for OPMODES 4,5,8
Determines the feed-forward factor for the position controller. Feed-forward is used to ease the task of the
position controller. A better setting for the Ff-factor means a better utilization of the dynamic range of the
position controller. The most favorable setting (usually about 1.0) depends on factors external to the drive, such
as friction, dynamic resistance, and stiffness.
KV
ASCII: GP
Default: 0,15 valid for OPMODES 4,5,8
Determines the proportional gain for the position controller.
Normalization: speed in m/s at 1 mm position deviation.
max.Following Error
ASCII: PEMAX
Default: 262144 valid for OPMODES 4,5,8
The following error is the maximum difference (+/- window) between the position setpoint and the actual position
that is permitted during processing. If the value leaves this window, then the position controller generates an
error message and brakes the drive, using the emergency ramp.
Mode / Position Feedback
ASCII: EXTPOS
Default: 0 valid for all OPMODES
Mode
Determines the type of position control loop (P/PI). With a PI position control, this screen page appears in a
different layout.
Position feedback
Determines the feedback source for the internal position controller. For most applications, the position infor-
mation for commutation and for position control are derived from the same source. This source is determined on
the "FEEDBACK" screen page, and can be either a resolver or an Endat/Hiperface encoder. In certain situa
-
tions it may be advisable to derive the position information for commutation from a different source to that for
the position control. In such a case the feedback parameter will continue to be the source for commutation, and
the source for the position control will be given by gearing mode.
Standard feedback
- Feedback type is set by feedback
- it is not possible to read in an encoder via X1 or X5
Read external (ROD/SSI) for fieldbus
- Feedback type is set by feedback, external encoder is set by gearing mode
External (ROD/SSI) for position control
- Feedback type is set by external source via gearing mode
56 Setup Software