5
5-5
Commonly used V/F Setting
(1) General Purpose
Factory Settings
Motor Spec. 60Hz
Pr.03
Pr.04
Pr.05
Pr.06
Pr.07
Pr.08
Pr.09
60.0
60.0
220.0
1.5
10.0
1.5
10.0
V
60.0 f
10
1.5
220
Pr.03
Pr.04
Pr.05
Pr.06
Pr.07
Pr.08
Pr.09
50.0
50.0
220.0
1.3
12.0
1.3
12.0
V
50.0 f
10
1.5
220
No.
No.
Motor Spec. 50Hz
Set value
Set value
(2) Fans and Pumps
Motor Spec. 60Hz
V
220
10
1.5
60.0f
Factory Settings
Set value
No.
Pr.03
60.0
Pr.04
60.0
Pr.05
220.0
Pr.06
30
Pr.07
50.0
Pr.08 1.5
Pr.09
10.0
30
50
Motor Spec. 50Hz
V
220
10
1.3
50.0f
Set value
No.
Pr.03
50.0
Pr.04
50.0
Pr.05
220.0
Pr.06
25
Pr.07
50.0
Pr.08 1.3
Pr.09
10.0
25
50
(3) High Starting Torque
Motor Spec. 60Hz
V
220
18
1.5
60.0f
Factory Settings
Set value
No.
Pr.03
60.0
Pr.04
60.0
Pr.05
220.0
Pr.06
3
Pr.07
23.0
Pr.08 1.5
Pr.09
18.0
3
23
Motor Spec. 50Hz
V
220
14
1.3
60.0f
Set value
No.
Pr.03
50.0
Pr.04
50.0
Pr.05
220.0
Pr.06
2.2
Pr.07
23.0
Pr.08 1.3
Pr.09
14.0
2.2
23
Pr.10
Acceleration Time 1
a
Factory Setting: 10.0
Pr.11
Deceleration Time 1
a
Factory Setting: 10.0
Pr.12
Acceleration Time 2
a
Factory Setting: 10.0
Pr.13
Deceleration Time 2
a
Factory Setting: 10.0
Settings 0.1 to 600.0 sec or 0.01 to 600.0 sec Unit: 0.1 or 0.01 sec