5-56
Pr.112 External Terminal Scanning Time
Factory Setting: 01
Settings 01 to 20
Unit: 2msec
This function screens the signal on I/O terminals for CPU malfunctions due to external
transients. A setting of 02, makes the scanning time to be 2 x 2 = 4 msec.
Set Pr.77 to 02 before changing settings in Pr.112.
Pr.113 Restart Method after Fault (oc, ov, BB)
Factory Setting: 01
Settings 00 None speed search
01 Continue operation after fault speed search from speed reference
02 Continue operation after fault speed search from Minimum speed
This parameter is used to select the restart method after certain faults.
Pr. 114 Cooling Fan Control
Factory Setting: 02
Settings 00 Fan Off when the drive stop after 1 Min
01 AC Drive Runs and Fan On, AC Drive Stops and Fan Off
02 Always Run
03 Reserved
Pr. 115 PID Set Point Selection
Factory Setting: 00
Settings 00 Disable
01 Keypad (based on Pr.00 setting)
02 AVI (external 0-10V)
03 ACI (external 4-20mA)
04 PID set point (Pr.125)
B550 Series sensorless vector frequency drive