EasyManua.ls Logo

Bedford B550-2002 - Control Source; Counter Reset; Parameter Disable

Default Icon
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-20
Note: The Counter Trigger input can be connected to an external Pulse Signal Generator when
counting a process step or unit of material. See the diagram below.
2ms
2ms
Indication value
(Pr.64=1)
Counter trigger signal
Multi-function input terminal
Signal output with Pr.97
counter value is attained.
(Pr.97=3)
(Pr.45/46=13)
Signal output with Pr.96
counter value is attained.
(Pr.96=5)
(Pr.45/46=14)
The trigger timing
can't be less than
2ms.(<250Hz)
(Pr.38 to Pr.42 =18)
19 Counter Reset:
Parameter value 19 programs Multi-Function Input Terminal: M1 (Pr.38), M2 (Pr.39), M3
(Pr.40), M4 (Pr.41) or M5 (Pr.42) to reset the counter.
GND
19 reset the
counter value.
Mx "close": reset counter.
Reset counter
20 Parameter Disable:
Enter value (20) to disable any Multi-Function Input Terminal: M1 (Pr.38), M2 (Pr.39), M3
(Pr.40), M4 (Pr.41) or M5 (Pr.42)
Note: Purpose of this function is to isolate unused Multi-Function Input Terminals. Any
unused terminals should be programmed to 20 to insure they have no effect on drive
operation.
22 Control Source: External Terminal / 23 Control Source: Keypad / 24 Control Source:
Communication:
Enter values 22, 23, or 24 to set the control source to be the external terminals, keypad or
communication respectively. This setting is used to create functions for manual/auto, and
remote/near-end control. When these three functions are used at the same time, the
priority is 22-I/O > 23-Keypad > 24-Communication.
B550 Series sensorless vector frequency drive

Table of Contents

Related product manuals