13 / EN
Local air-conditioner / User Manual
2. Instructons for reparng applances contanng
R290
the refrgerant contanng parts are nstalled; the
ventlaton machnery and outlets are operatng
adequately and are not obstructed; f an ndrect
refrgeratng crcut s beng used, the secondary
crcut shall be checked for the presence of
refrgerant; markng to the equpment contnues
to be vsble and legble. Markngs and sgns that
are llegble shall be corrected; refrgeraton
ppe or components are nstalled n a poston
where they are unlkely to be exposed to any
substance whch may corrode refrgerant
contanng components, unless the components
are constructed of materals whch are nherently
resstant to beng corroded or are sutably
protected aganst beng so corroded.
2.1.9 Checks to electrcal devces
Repar and mantenance to electrcal components
shall nclude ntal safety checks and component
nspecton procedures. If a fault exsts that could
compromse safety, then no electrcal supply shall
be connected to the crcut untl t s satsfactorly
dealt wth. If the fault cannot be corrected
mmedately but t s necessary to contnue
operaton, an adequate temporary soluton shall
be used. Ths shall be reported to the owner of
the equpment so all partes are advsed.
Intal safety checks shall nclude: that capactors
are dscharged: ths shall be done n a safe manner
to avod possblty of sparkng; that there no lve
electrcal components and wrng are exposed
whle chargng, recoverng or purgng the system;
that there s contnuty of earth bondng.
2.2 Repars to sealed components
2.2.1 Durng repars to sealed components,
all electrcal supples shall be
dsconnected from the equpment
beng worked upon pror to any removal
of sealed covers, etc. If t s absolutely
necessary to have an electrcal supply
to equpment durng servcng, then
a permanently operatng form of leak
detecton shall be located at the most
crtcal pont to warn of a potentally
hazardous stuaton.
2.2.2 Partcular attenton shall be pad to the
followng to ensure that by workng
on electrcal components, the casng s
not altered n such a way that the level
of protecton s affected. Ths shall
nclude damage to cables, excessve
number of connectons, termnals
not made to orgnal specfcaton,
damage to seals, ncorrect fttng of
glands, etc. Ensure that apparatus s
mounted securely. Ensure that seals
or sealng materals have not degraded
such that they no longer serve the
purpose of preventng the ngress of
flammable atmospheres. Replacement
parts shall be n accordance wth the
manufacturer’s specfcatons.
C
Note:
The use of slcon sealant
may nhbt the effectveness
of some types of leak detecton
equpment. Intrnscally safe
components do not have to be
solated pror to workng on
them.
2.3 Repar to ntrınsıcally safe
components
Do not apply any permanent nductve or
capactance loads to the crcut wthout ensurng