Ensure that the outlet for the vacuum pump s
not close to any gnton sources and there s
ventlaton avalable.
2.8 Chargng procedures
In addton to conventonal chargng
procedures,the followng requrements shall be
followed.
– Ensure that contamnaton of dfferent
refrgerants does not occur when usng
chargng equpment. Hoses or lnes shall
be as short as possble to mnmze the
amount of refrgerant contaned n them.
– Cylnders shall be kept uprght.
– Ensure that the refrgeraton system s
earthed pror to chargng the system wth
refrgerant.
– Label the system when chargng s
complete (f not already).
– Extreme care shall be taken not to overfll
the refrgeraton system.
Pror to rechargng the system t shall be
pressure tested wth OFN. The system shall be
leak tested on completon of chargng but pror
to commssonng. A follow up leak test shall be
carred out pror to leavng the ste.
2.9 Decommssonng
Before carryng out ths procedure, t s essental
that the techncan s completely famlar wth the
equpment and all ts detal. It s recommended
good practce that all refrgerants are recovered
safely. Pror to the task beng carred out, an ol
and refrgerant sample shall be taken n case
analyss s requred pror to re-use of reclamed
refrgerant. It s essental that electrcal power s
avalable before the task s commenced.
a) Become famlar wth the equpment and
ts operaton.
b) Isolate system electrcally.
c) Before attemptng the procedure ensure
that: mechancal handlng equpment
s avalable, f requred, for handlng
refrgerant cylnders; all personal
protectve equpment s avalable and
beng used correctly; the recovery process
s supervsed at all tmes by a competent
person; recovery equpment and cylnders
conform to the approprate standards.
d) Pump down refrgerant system f possble.
e) If a vacuum s not possble, make a manfold
so that refrgerant can be removed from
varous parts of the system.
f) Make sure that cylnder s stuated on the
scales before recovery takes place.
g) Start the recovery machne and operate
n accordance wth manufacturer’s
nstructons.
h) Do not overfll cylnders. (No more than 80 %
volume lqud charge).
) Do not exceed the maxmum workng
pressure of the cylnder,even temporarly.
j) When the cylnders have been flled
correctly and the process completed, make
sure that the cylnders and the equpment
are removed from ste promptly and all
solaton valves on the equpment are
closed off.
k) Recovered refrgerant shall not be charged
nto another refrgeraton system unless t
has been cleaned and checked.
2.10 Labellng
2. Instructons for reparng applances contanng
R290