Modbus register
44
RCMB300-series_D00372_01_M_XXEN/06.2019
Notes:
1)
Register 16074 "Filter mode"
2)
Registers 16075 and 16076: If contact monitoring is active, the disconnected state is always
checked after 500 ms (not configurable). If and when the connected state is checked
depends on register 16076.
3)
Is not saved when the device is switched off.
Register
entry
Meaning
Adjustable
RCMB 301
1 Normal (full bandwidth: 100 kHz) X
2Low-pass 60 Hz X
3 Low-pass 500 Hz X
4Low-pass 1 kHz X
5Low-pass 2 kHz X
6Low-pass 5 kHz X
7Low-pass 10 kHz X
8Low-pass 20 kHz X
9Low-pass 50 kHz X
10 Type B X
11 Reserved
12 Type B+ (up to 100 kHz) X
13 Reserved
14 Fire protection (up to 100 kHz) X
15…16 Reserved
17 Low-pass 180 Hz X