EasyManua.ls Logo

Bender RCMB300 Series - Device Parameters and Factory Settings

Bender RCMB300 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus register
40
RCMB300-series_D00372_01_M_XXEN/06.2019
7.6 Device parameters and factory settings
t
on9
= response delay t
off
= delay on release
Register
Property
Format
Description
Value range
Unit
{Step size}
Factorysettings
RCMB301
16000 RW
Float32
AC
Limit value
alarm
0.03…3.00 A
{1 mA}
0.03
16002 RW
Limit value
prewarning
50 … 100 %
{1 %}
60 %
16004 RW Hysteresis
10 … 25 %
{1 %}
15 %
16006 RW
t
on
alarm MRCDB:
0 s… 60 min
RCMB:
50 ms…60 min
{10 ms}
50 ms
16008 RW
t
on
prewarning
1 s
16010 RW
t
off
(pre)alarm
16012 RW
DC
Limit value
alarm
0.03…3.00 A
{1 mA}
0.03 A
16014 RW
Limit value
prewarning
50 … 100 %
{1 %}
16016 RW Hysteresis
10 … 25 %
{1 %}
15 %
16018 RW
t
on
alarm MRCDB:
0 s… 60 min
RCMB:
50 ms…60 min
{10 ms}
50 ms
16020 RW
t
on
prewarning
1 s
16022 RW
t
off
(pre)alarm
16024 RW
Float32
RMS
Limit value
alarm
0.03 … 3.00 A
{1 mA}
0.03 A
16026 RW
Limit value
prewarning
50 … 100 %
{1 %}
60 %
16028 RW Hysteresis
10 … 25 %
{1 %}
15 %
16030 RW
t
on
alarm MRCDB:
0 s… 60 min
RCMB:
50 ms…60 min
{10 ms}
50 ms
16032 RW
t
on
prewarning
1 s
16034 RW
t
off
(pre)alarm
16036 RW Start-up delay
0 … 3600 s
{10 ms}

Table of Contents

Related product manuals