41
RCMB300-series_D00372_01_M_XXEN/06.2019
16038 RW
UINT16
Relay 1
Relay mode
1 = N/C principle
2 = N/O principle
16039 RW
Alarm assignment
start alarm
Alarm assignment
1 = inactive
2 = active
16040 RW
Alarm assignment
device error
16041 RW Alarm assignment test
16042 RW
Alarm assignment
limit value violation I
Δn
prewarning (AC)
16043 RW
Alarm assignment
limit value violation I
Δn
prewarning (DC)
16044 RW
Alarm assignment
limit value violation I
Δn
prewarning (RMS)
16045…16054 Reserved
16055 RW
UINT16
Fault memory mode
1)
1 = off
2 = on
3 = permanent
Register
Property
Format
Description
Value range
Unit
{Step size}
Factorysettings
RCMB301

Table of Contents