EasyManua.ls Logo

Bender RCMB300 Series - Page 42

Bender RCMB300 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus register
42
RCMB300-series_D00372_01_M_XXEN/06.2019
16056 RW
UINT16
Relay 2
Relay mode
1 = N/C principle
2 = N/O principle
1
16057 RW
Alarm assignment
start alarm
Alarm assignment
1 = inactive
2 = active
16058 RW
Alarm assignment
device error
16059 RW Alarm assignment test
16060 RW
Alarm assignment
limit value violation I
Δn
prewarning (AC)
16061 RW
Alarm assignment
limit value violation I
Δn
prewarning (DC)
16062 RW
Alarm assignment
limit value violation I
Δn
prewarning (RMS)
16063…16072 Reserved
16073 RW
UINT16
Fault memory
mode
1 = off
(only …303 and…304)
2 = on
3 = permanent
2
16074 RW
UINT16
Filter
mode
1) 4
16075 RW
Function
contact monitoring
2)
1 = off
2 = N/C
3 = N/O
16076 RW
Float32
t
off
(contact monitoring)
2)
0 (= off)
0.01…3600 s
Seconds
Time delay after which the
connected relay state is
monitored.
{10 ms}
Register
Property
Format
Description
Value range
Unit
{Step size}
Factorysettings
RCMB301

Table of Contents

Related product manuals