Page #42 background image
Modbus register
42
RCMB300-series_D00372_01_M_XXEN/06.2019
16056 RW
UINT16
Relay 2
Relay mode
1 = N/C principle
2 = N/O principle
1
16057 RW
Alarm assignment
start alarm
Alarm assignment
1 = inactive
2 = active
16058 RW
Alarm assignment
device error
16059 RW Alarm assignment test
16060 RW
Alarm assignment
limit value violation I
Δn
prewarning (AC)
16061 RW
Alarm assignment
limit value violation I
Δn
prewarning (DC)
16062 RW
Alarm assignment
limit value violation I
Δn
prewarning (RMS)
16063…16072 Reserved
16073 RW
UINT16
Fault memory
mode
1 = off
(only …303 and…304)
2 = on
3 = permanent
2
16074 RW
UINT16
Filter
mode
1) 4
16075 RW
Function
contact monitoring
2)
1 = off
2 = N/C
3 = N/O
16076 RW
Float32
t
off
(contact monitoring)
2)
0 (= off)
0.01…3600 s
Seconds
Time delay after which the
connected relay state is
monitored.
{10 ms}
Register
Property
Format
Description
Value range
Unit
{Step size}
Factorysettings
RCMB301

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender RCMB300 Series and is the answer not in the manual?

Bender RCMB300 Series Specifications

General IconGeneral
BrandBender
ModelRCMB300 Series
CategoryControl Unit
LanguageEnglish

Related product manuals