Technical data VME420…
45
VME420_D00026_03_M_XXDE/04.2019
Switching elements
Number of changeover contacts............................................................................................................... 2 x 1 (K1, K2)
Operating principle ....................................................................................................... N/C operation / N/O operation
.......................................................... K2: Err, < U, > U, < Hz, > Hz, S.AL (undervoltage < U: N/C operation n.c.)*
............................................................ K1: Err, < U, > U, < Hz, > Hz, S.AL (overvoltage > U: N/O operation n.o.)*
Electrical endurance........................................................................................................... 10000 switching operations
Contact data acc. to IEC 60947-5-1:
Utilisation category ......................................................................... .. AC 13..... AC 14 ..... DC-12 .... DC-12..... DC-12
Rated operational voltage .............................................................. .. 230 V..... 230 V ........ 24 V ..... 110 V..... 220 V
Rated operational current................................................................ ...... 5 A......... 3 A .......... 1 A ...... 0.2 A...... 0.1 A
Minimum contact rating ............................................................................................................ 1 mA at AC/DC ≥ 10 V
Environment/EMC
EMC ................................................................................................................................................................. IEC 61326
Operating temperature ...................................................................................................................... -25 ºC…+55 ºC
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ........................................................3K5 (except condensation and formation of ice)
Transportation (IEC 60721-3-2) ..................................................... 2K11 (except condensation and formation of ice)
Storage (IEC 60721-3-1) ................................................................. 1K22(except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .............................................................................................................................. 3M4
Transportation (IEC 60721-3-2) .............................................................................................................................. 2M4
Storage (IEC 60721-3-1) .......................................................................................................................................1M12
Option "W" data different from the standard version
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................. 3K5 (condensation and formation of ice is possible)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ............................................................................................................................. 3M7