44
Bentone BF1
General
9.1.3 Technical data
LMO14 LMO24 LMO44
Pre-ignition period:
15 s 25 s 25 s
Pre-ventilation period:
16 s 26 s 26 s
Post-ignition period:
10 s 5 s 5 s
Safety period:
< 10 s < 5 s < 5 s
Re-connection after release:
< 1 s < 1 s < 1 s
Reaction time flame extinction:
< 1 s < 1 s < 1 s
Ambient temperature:
-5 - +60°C -5 - +60°C -20 - +60°C
Min. current with flame:
45 µA dc 45 µA dc 45 µA dc
Max current when dark, start:
5,5 µA dc 5,5 µA dc 5,5 µA dc
Photocell current checks
Photocell current is measured with a direct current ammeter
(mulitimeter μA) connected in series with the photocell.