59
No. Name lower upper default UOM Description
limit limit settinglimit limit setting
26 CH_low_hyst_on 0 20 5 °C Start hysteresis in low circuit calculated
on the mixer outlet temp
27 CH_low_hyst_off 0 20 3 °C Stop hysteresis in low circuit calculated
on the mixer outlet temp
28
Mix_valve_step_ open_time
0 255 5 s For each step the valve opens
1/2 of the set value
29
Mix_valve_step_close_time
0 255 7 s For each step the valve closes
1/2 of the set value
30 Mix_valve_interval_time 0 255 5 s Mixing valve delay
31 Mixing_p_hyst 0 255 2 °C Hysteresis for maximum valve opening
32 Mixing_still_hyst 0 255 2 °C
33 Power control mode 0 1 1 0 = Minimum number of burners
1 = Maximum number of burners
34 3
rd
pump 0 1 0 0 = System/loop
1 = Low temperature circuit
35 Frost protection -30 15 3 °C System
36 Gas_type 1 31 01 01 = NG with flue < 15m
02 = NG with flue > 15m
03 = LPG with flue < 15m
04 = LPG with flue > 15m
37 T_out_min -20 30 0 °C
38 T_out_max 0 30 18 °C
39 T_out_correct -30 30 0 °C
40 T_emergency 10 80 70 °C
41 Parameter_reset 0 1 0
42 Flow switch on slave 0 1 1 0 = The slave does not control the pressure switch
43 Protocol 0 1 1 0 = Eco protocol
1 = Argus link (new)