Beretta POWER PLUS - Parameter Reference (Continued); Installer Parameters List (Part 2)

Beretta POWER PLUS
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
No. Name lower upper default UOM Description
limit limit settinglimit limit setting
26 CH_low_hyst_on 0 20 5 °C Start hysteresis in low circuit calculated
on the mixer outlet temp
27 CH_low_hyst_off 0 20 3 °C Stop hysteresis in low circuit calculated
on the mixer outlet temp
28
Mix_valve_step_ open_time
0 255 5 s For each step the valve opens
1/2 of the set value
29
Mix_valve_step_close_time
0 255 7 s For each step the valve closes
1/2 of the set value
30 Mix_valve_interval_time 0 255 5 s Mixing valve delay
31 Mixing_p_hyst 0 255 2 °C Hysteresis for maximum valve opening
32 Mixing_still_hyst 0 255 2 °C
33 Power control mode 0 1 1 0 = Minimum number of burners
1 = Maximum number of burners
34 3
rd
pump 0 1 0 0 = System/loop
1 = Low temperature circuit
35 Frost protection -30 15 3 °C System
36 Gas_type 1 31 01 01 = NG with flue < 15m
02 = NG with flue > 15m
03 = LPG with flue < 15m
04 = LPG with flue > 15m
37 T_out_min -20 30 0 °C
38 T_out_max 0 30 18 °C
39 T_out_correct -30 30 0 °C
40 T_emergency 10 80 70 °C
41 Parameter_reset 0 1 0
42 Flow switch on slave 0 1 1 0 = The slave does not control the pressure switch
43 Protocol 0 1 1 0 = Eco protocol
1 = Argus link (new)