BA-EN-HydroStar V3.1 page 18
7.3 Motor connection
• Insert the motor cable into the M25 threaded cable connection so that the jacket is pushed
through by approximately 50 mm.
• Securely tighten the threaded cable connection.
• Connect the motor supply line to the terminal strip according to the colour coding.
7.4 Extending the motor supply line
NOTE: Observe the minimum cross-section of 16 mm²!
If it is necessary to lengthen the line, observe the motor's rotation direction.
If the turbine is running in the wrong direction, invert the two connection lines.
• Shorten the original motor supply (3 x 6mm²) line to ≤ 5 m (minimum 2 m)
• Extend up to a total length of 30 m with a cable cross-section of 16 mm²
fine wired!
• To extend the turbine cable, the original BINDER 3x16 mm² cable is recommended! (Art.
No.: 5300115)
7.5 Connecting the HydroStar PIEZO Tri
• The connection cable is a 14-wire cable with cross-section of 0.5 mm
2
.
• The cable can be lengthened with an equivalent cable up to 30 m.
• It must be ensured that the wires are connected with the same numbering.
• An underground junction box for cable lengthening must have a watertight seal.
• Terminal strip X2 is used for connection.
• Connect the wire number according to terminal number.
• Please also observe the circuit diagrams included in delivery!
NOTE: Please also observe the circuit diagrams included in delivery!