DB-300-9 9
Type Reservoir fluid
capacity
dm
3
(l)
Category according
to 2014/68/EU (PED)
Fluid group 2
Category according
to 2014/68/EU (PED)
Fluid group 1
Conformity as-
sessment de-
pending on the
module
FS4752(P) 473 IV IV B + D
FS5502(P) 550 IV IV B + D
OA1954(A) 40 III IV B + D
OA4188(A) 88 III IV B + D
OA9111(A) 228 IV IV B + D
OA14111(A) 395 IV IV B + D
OA25112(A) 655 IV IV G
OAC14011A 616 IV IV G
OAC25112A 868 IV IV G
OAS322 2.7 I II A2
OAS744 7 I II A2
OAS1055 10 II III B + D
OAS1655 16 II III B + D
OAS3088 30 II III B + D
OAF6288 62 III IV B + D
OAF15211 152 IV IV B + D
OAH2888 112 IV IV B + D
OAH7088 228 IV IV B + D
OAHC65051A 630 IV IV B + D
OAHC80051A 1130 IV IV G
OAHC100051A 2250 IV IV G
Tab.2: Category and conformity assessment
4 Mounting
4.1 Transporting the pressure vessel
Transport the pressure vessel screwed on a pallet. Lift
it using the eyebolts or the upper fastening brackets if
available.
DANGER
Suspended load!
Do not step under the machine!
4.2 Installation location
For outdoor installation, take suitable measures to pro-
tect the pressure vessel against corrosion (e.g. caused
by seawater or aggressive atmosphere) and low out-
side temperatures. Consultation with BITZER is recom-
mended.