Attention! When output external control of ‘S2000-4’, ‘Signal-20P’ and ‘Signal-20’
version 02 devices is used internal control has to be removed, that is outputs have to be not
connected to loops. If internal output control is used it is prohibited to use external control, that
is outputs have to be not connected to partitions.
Relay output is set on the tab ‘Relay’ of program ‘pprog.exe’. Tab contains two windows:
in top window ‘Partitions (relay)’ is displayed partition tree, where for each partition is shown
connected relay list. Bottom window ‘Devices (relay)’ contains tree of all system devices with
relays. To connect relay output with partition, ‘drag’ the relay from device tree (window
‘Devices (relay)’) in corresponded partition in the tree (window ‘Partitions (relays)’). At that
relay will be added to the connected partition list. If output should be controlled by few
partitions, connect it with other partitions the same way. It is possible group connection
partitions and outputs. Few output can be selected by left mouse button and pressed key ‘Shift’
(for range selection) or ‘Ctrl’ (for selective marking), after that there can de added to the
partition. At ‘dragging’ output or few outputs on the tree ‘root’ ‘Partition (relays)’ will be
connected to the all partitions in the system. At ‘dragging’ device to the partition all device
outputs will be connected to the partition. Also control program, start delay, and control time for
the outputs should be set. For that in the window ‘Devices (relays)’ in device tree select relay, in
the inspector window are displayed current parameter values, correct them if necessary.
2.1.7.5 Setting message transmission
It is possible transmit events to ‘S2000-K’ keyboard version 1.04 and above. Keyboards
allow indicating received events on LCD, signalize by internal sound annunciator at alarm event,
have nonvolatile event buffer. Messages can be transmitted to ‘S2000-IT’ phone informators.
Messages should not sent to the other devices, because they are not needed them for work and
delay system operability! For setting events transition to the devices select the devices, which
will receive messages from the console. Messages can be sent independently (translation to the
address), or like broadcast message to all devices at once (common translation). For each device
message categories and partitions for transmission can be set. It allows permitting some type
message transitions (for example, alarms and fires) and prohibit another ones (for example,
arm/disarm alarm loop). Message categories are in appendix Г. Partition list allows send only the
messages from loop of this list.
Message transition is set on tab ‘Event translation’ program ‘pprog.exe’. Top window
‘Event transition’ contain list of devices for message transition from console. Each device has to
have transition permitted partition list. Bottom window can display either system device list
(‘Devices’), or partition list ‘Partitions’. Device list is used for adding devices in message device
list (in window ‘Event transition’). At adding device tree node ‘To all devices’ console messages
will be receive all system devices. Its unload RS-485 line at transmission the same messages to
the large number of devices, but exclude individual message send. For each device, added in
window ‘Message transition’, in inspector next message categories are pointed, which will be
transmitted to it. Also for each device list of permitted message sources (partitions) should be
set. For that in bottom window select partition list and ‘drag’ selected devices.
Also, event transmission to printer can be required. This setting is selection of event
category that has to be printed. Default value is all events are printed.
Attention!
1) Message transition heavily load RS-485 interface, that decrease system operation
speed. To unload interface need to transmit just rare events (such as alarms, fires, faults), use
transmission ‘To all devices’, to transmit messages large number of devices.