FIRE AND ALARM CONSOLE
32
2.1.7.9 Using the console for creating of systems controlling gas, powder or aerosol
fire extinguishing installations based on "S2000-ASPT" devices
The console is suitable in gas, powder or aerosol fire extinguishing systems based on
"S2000-ASPT" devices especially in case of using several extinguishing areas at once. The
console can be used in such systems as follows:
1) To indicate system status by means of "S2000-PТ" devices each displaying the current
status of 10 areas of extinguishing. For each area several status are displayed, among them fires,
faults of fire loops, output circuits, primary and standby power supply, launch blocking, fire
extinguishing launching mode (manual or auto), various statuses of launching ("Launching
delay", "Launching", "Extinguishing", "Launch fault").
2) To control the status of fire extinguishing area, turn auto/manual launching mode and
activate/cancel remote launching from console itself or "S2000-PT" device. These functions
require password-based access.
3) The console has a number of relay control programs designed for operating in fire
extinguishing systems. Programs "Turn on/off when auto extinguishing is on/off" monitor the
launching mode of fire extinguishing units and can be used in particular for controlling "Manual
extinguishing" light box. Programs "Turn on during launching delay" and "Turn on during
extinguishing" can be used for "Keep out!" и "Get out!" light annunciator controlling. The
program "Turn on during launching" can be used for launching of extinguishing installation for
several areas. The program "Turn on if launching failed" can be used for standby fire
extinguishing installation launching.
It is recommended to use "S2000-ASPT" versions 2.03 and above along with "S2000М"
console. The controlling of "S2000–ASPT" devices with versions less than 2.00 is limited by
automatic launching control mode and remote launch in local control mode only (out of
partitions). Such control doesn’t require the configuring of the console and described in section
2.2.3.4.
All zones of “S2000–ASPT” (loops, inner zones and output circuits) should be combined
into one partition which represents one area or fire extinguishing. It is necessary to assign some
passwords for launch mode control operations and for activating/canceling of the remote launch.
For this purpose when creating authority levels ("Authority levels" tab in "pprog.exe") define
partitions that is permitted for controlling (that is extinguishing areas) and assign the permitted
operations for each partition. The permitted operations can be arming, disarming, and turning
automatic equipment on, turning automatic equipment off, remote launching and launch
canceling. Arming is needed for resetting of activated "S2000–ASPT" loops. Disarming is
meaningless in the context of "S2000–ASPT" using. Other operations are given when needed.
When using "S2000–PT" it is necessary to assign the partition number to each indicator
group by means of "uprog.exe". Hence the indicator group is associated with the specific
extinguishing area and displays the status of that area. The "FIRE" indicator shows either if some
fire loops of "S2000–ASPT" have been activated (being in "FIRE" or "FIRE PREALARM"
status), or control zone state (when remote launching command from console has been received
), or manual call point activated. "FAULT" indicator signals if there are various troubles in
extinguishing area, among them fire loop troubles, output circuit troubles, power outage and
disconnection from "S2000–ASPT". "LAUNCH BLOCKED" indicator displays if there is
extinguishing launching blocking up (e.g., during launching delay doors to the protected