8 Technical Data
Detector overview
FAP-425-
DOTCO-R
FAP-425
-DOTC-R
FAP-425
-DOT-R
FAP-425
-DO-R
FAP-425
-OT-R
FAP-425
-OT
FAP-425
-O-R
FAP-425
-O
FAH-425
-T-R
Scattered-light
measurement
X X X X X X X X -
Measurement
of absolute
temperature
and
temperature
increase
X X X - X X - - X
Combustion
gas
measurement
X X - - - - - - -
Two optical
sensors
X X X X - - - - -
Contamination
detection
X X X X X X X X -
Drift
compensation
in the optical
sensor
X X X X X X X X -
Operation
mode
switching/
sensor
deactivation in
optical unit
and thermal
unit
X X X - X X - - -
Electrical
Operating voltage 15VDC to 33VDC
Current consumption 0.55mA
Alarm output Per dataword by two‑wire signal line.
Indicator output Open collector connects 0V over 1.5kΩ through, max. 15mA.
Response sensitivity
The detector is adjustable to different sensitivity levels. Default settings are for medium
sensitivity level.
FAP-425-
DOTCO-R
FAP-425
-DOTC-R
FAP-425
-DOT-R
FAP-425
-DO-R
FAP-425
-OT-R
FAP-425
-OT
FAP-425
-O-R
FAP-425
-O
FAH-425
-T-R
Optical sensor Average <0.15dB/m (EN54-7)