38 en | Technical Data AVENAR detector 4000
2023-06 | 07 | F.01U.283.550
User manual
Bosch Sicherheitssysteme GmbH
FAP-425-
DOTCO-R
FAP-425
-DOTC-R
FAP-425
-DOT-R
FAP-425
-DO-R
FAP-425
-OT-R
FAP-425
-OT
FAP-425
-O-R
FAP-425
-O
FAH-425
-T-R
Max.<0.18dB/m (EN54-7)
Thermal
differential
unit
EN54‑5 EN54‑5 EN54‑5 - EN54‑5 EN54‑5 - - EN54‑5
Thermal
maximum unit
>54°C /
>69°C
>54°C
/
>69°C
>54°C
/
>69°C
- >54°C
/
>69°C
>54°C
/
>69°C
- - >54°C
/
>69°C
Chemical
Sensor
ppm
range
ppm
range
- - - - - - -
Environmental
FAP-425-
DOTCO-R
FAP-425
-DOTC-R
FAP-425
-DOT-R
FAP-425
-DO-R
FAP-425
-OT-R
FAP-425
-OT
FAP-425
-O-R
FAP-425
-O
FAH-425
-T-R
Monitoring
area (m²)
(observe VdS
guidelines)
120 m
2
40 m²
Installation
height (m)
(observe VdS
guidelines)
Max. 16 m 0 m –
7.50 m
Permissible air
speed (m/s)
20 m/s -
Storage
temperature
(°C)
-20 °C –
50 °C
-20 °C –
50 °C
-25 °C –
80 °C
-25 °C –
80 °C
-25 °C –
80 °C
-25 °C –
80 °C
-25 °C –
80 °C
-25 °C –
80 °C
-25 °C –
80 °C
Operating
temperature
(°C)
-10 °C –
50 °C
-10 °C –
50 °C
-20 °C –
50 °C
-20 °C –
65 °C
-20 °C –
50 °C
-20 °C –
50 °C
-20 °C –
65 °C
-20 °C –
65 °C
-20 °C –
50 °C
Operating
relative
humidity, non-
condensing
(%)
15% –
90%
15% –
90%
15% –
95%
15% –
95%
15% –
95%
15% –
95%
15% –
95%
15% –
95%
15% –
95%
IP rating (IEC
60529)
IP41 , IP43 with detector base and FAA-420-SEAL or MSC 420
Mechanical
FAP-425-
DOTCO-R
FAP-425
-DOTC-R
FAP-425
-DOT-R
FAP-425
-DO-R
FAP-425
-OT-R
FAP-425
-OT
FAP-425
-O-R
FAP-425
-O
FAH-425
-T-R
Ring color
code
2x pastel
blue
2x
yellow
2x black 2x grey 1x black 1x black - - 1x red