62 en | System limits AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
LSN elements Max. number
Per network panel 1016
Total network 32512
Detection points Max. number
EN 54 compliant panel 512
Stand-alone panel, not EN54 compliant 4096
Networked panel, not EN 54 compliant 2048
Total network 32768
NAC groups Max. number
NAC groups with more than one FNM-420, per loop 6
Voice alarm system Max. number
In CAN network, per panel (premium license) 1
In total Ethernet network (premium license) 1
Triggers (each trigger counts as one sounder group)
Ethernet interface
244
Triggers (each trigger counts as one sounder group)
RS-232 interface
120
Per fire panel Max. number
Sets, e.g. bypass group
These sets include sets which are automatically created for each
LSN bus.
192
Functional modules 6
Printer 4
Alarm counters (external, internal, testing) 3
Entries in the event database 10000
FSP-5000-RPS configuration interfaces (USB) 1
Maximum number of outputs (sounders, controls, etc.) activated in
parallel due to the same event
508
Configuration limits per fire panel (FSP-5000-RPS) Max. number
Timer channels 20
Time control programs 19
Configuration for a Specific Day 365
Permission levels 4
User profiles 200
Sum counters and counters (in total) 60000