40 en | Planning AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
0
200
400
600
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250
N
Figure3.4: Diagram for determining the maximum achievable cable length: LSN improved elements with LSN 1500 A
L = cable length in meters
N = number of LSN improved elements
a = Bus dynamic limit
b = maximum possible number of LSN improved elements = 254
3.9 Configuration with BCM-0000-B modules
AVENAR panel 8000 can be powered by up to 8 BCM-0000-B battery controller modules, each
with its own UPS 2416 A power supply unit. Current consumption is equally distributed among
all battery controller modules.
Notes
– The 24V switch outputs may not be connected in parallel.
– The total current for all connected components including the battery charge current may
not exceed 6A.
– The batteries connected to the BCM must all be of the same type and have identical
electrical properties.
– The cable length at the switch outputs for faults may not exceed 3meters.
– The cables for the switch outputs for faults may only be routed inside the housing.
Configuration with 1 to 4 BCM-0000-B modules in wall mounting housings
– Up to 2 BCM-0000-B modules on short panel rail
– Maximum 2 BCM-0000-B modules at the end of the long panel rail
– Each BCM-0000-B module requires one UPS 2416 A power supply unit.