66 en | Appendix AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
8 Appendix
8.1 Options with requirements under EN 54‑2:1997/A1:2006
The panel provides the following options with requirements under EN 54‑2:1997/A1:2006:
– Output for activation of fire alarm devices
– Activation of fire alarm transmission equipment
– Output to fire alarm transmission equipment
– Alarm acknowledgement input from fire alarm transmission equipment
– Output for activation of fire protection equipment
– Output type B
– Output type C
– Fault monitoring of fire protection equipment
– Transmission delay
– Dependency of fire detection status on more than one alarm signal
– Type A dependency
– Type B dependency
– Type C dependency
– Alarm counter
– Fault signal status
– Fault signals from detection points
– Complete failure of power supply
– Output to fault signaling transmission equipment
– Disabled status
– Disabling of addressable points
– Test status
– Daymode status
8.2 Controlling Extinguishing Systems
The fire panel enables the activation of extinguishing systems with the extinguishing interface
described in VDE0833 Part2 or by the VdS (standard interface SST in line with VdS 2496).
Connection occurs with the FLM-420-RLE-S Extinguishing module.
For each LSN loop, a maximum of 8 extinguishing systems can be activated in each case with
an FLM-420-RLE-S Extinguishing module.
The requirement is for a maximum of one extinguishing area to fail in the case of a system
fault. This means that from the second extinguishing area, there must be a redundant panel
controller.
If several FLM-420-RLE-S Extinguishing modules are used to control the extinguishing system
in each LSN loop, in addition to the redundant panel controller, the associated LSN 0300 A or
LSN 1500 A module must also be duplicated.