60 en | System limits AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
7 System limits
7.1 System limits AVENAR panel 8000
Panels/remote keypads/OPC servers in the network Max. number
Ethernet / CAN 32
LSN elements Max. number
Stand-alone panel 4096
Per network panel 2048
Total network 32768
Detection points Max. number
Panel, without panel redundancy 512
Stand-alone panel, with panel redundancy 4096
Networked panel, with panel redundancy 2048
Total network 32768
NAC groups Max. number
NAC groups with more than one FNM-420, per loop 6
Voice alarm system Max. number
In CAN network, per panel (premium license) 1
In total Ethernet network (premium license) 1
Triggers (each trigger counts as one sounder group)
Ethernet interface
244
Triggers (each trigger counts as one sounder group)
RS-232 interface
120
Per fire panel Max. number
Sets, e.g. bypass group
These sets include sets which are automatically created for each
LSN bus.
192
Functional modules (with panel redundancy) 42
Functional modules 46
Printer 4
Alarm counters (external, internal, testing) 3
Entries in the event database 10000
FSP-5000-RPS configuration interfaces (USB) 1
Maximum number of outputs (sounders, controls, etc.) activated in
parallel due to the same event
508